Issue Date: November 22, 1995
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)
SiteSentinel
Controller
with
Hydrocarbon
Sensitive Polymer Cables
Part #30-3206,
Part #30-3207-nn,
Part #30-3210-nn,
Part #30-3219-12
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Output type:
|
qualitative
|
Sampling
frequency:
|
continuous
|
Operating
principle:
|
product permeable
|
Test Results:
Part
#30-3206, Part #30-3207-nn***, Part #30-3210-nn***, Part #30-3219-12.
|
unleaded
gasoline
|
diesel
|
Detection
time (min)
|
13.602
|
24.104
|
Fall
time (min)
|
*
|
**
|
*
Sensor must be cleaned and dried when exposed to hydrocarbons.
**
Sensor must be replaced or threshold needs to be reset when exposed to diesel.
***
“nn” denotes a variable length in feet.
Specificity
Results:
Evaluator
indicates that sensors respond only to hydrocarbons.
Comments:
Evaluator
indicates that since each of the sensors use the same polymer material, the
results can be applied to any sensor with this material.
OPW Fuel Management Systems
|
Evaluator:
Underwriters Laboratories, Inc.
|
6900 Santa Fe Dr.
|
Tel: (847) 272-8800
|
Hodgkins, IL 60525-9909
|
Date
of Evaluation: 12/10/92
|
Tel: (708) 485-4200
|
Evaluator:
Ken Wilcox Associates
|
E-Mail:
info@opwfms.com
|
Tel:
(816) 443-2494
|
URL: www.opwfms.com
|
Date
of Evaluation: 8/3/00
|
|