Issue Date: November 22, 1995
Revision Date: October 18, 2002

OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)

SiteSentinel Controller with Hydrocarbon Sensitive Polymer Cables
Part #
30-3206, Part #30-3207-nn, Part #30-3210-nn, Part #30-3219-12

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

 

Detector:           

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable  

Test Results:

Part #30-3206, Part #30-3207-nn***, Part #30-3210-nn***,  Part #30-3219-12.

 

unleaded gasoline

 

diesel

Detection time (min)

13.602

24.104

Fall time (min)

*

**

* Sensor must be cleaned and dried when exposed to hydrocarbons.
** Sensor must be replaced or threshold needs to be reset when exposed to diesel.
*** “nn” denotes a variable length in feet.

Specificity Results:
Evaluator indicates that sensors respond only to hydrocarbons.

Comments:
Evaluator indicates that since each of the sensors use the same polymer material, the results can be applied to any sensor with this material.

 

OPW Fuel Management Systems

Evaluator:  Underwriters Laboratories, Inc.

6900 Santa Fe Dr.

Tel:  (847) 272-8800

Hodgkins, IL 60525-9909

Date of Evaluation:  12/10/92

Tel:  (708) 485-4200

Evaluator:  Ken Wilcox Associates

E-Mail:  info@opwfms.com 

Tel:  (816) 443-2494

URL:  www.opwfms.com 

Date of Evaluation:  8/3/00

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.