Issue Date: November 22, 1995
Revision Date: October 18, 2002

OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)

Petrosentry IV, Petrosentry VIII, SiteSentinel with
Liquid Sensor, Universal Sump Sensor, Universal Reservoir Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:           

Output type:

qualitative

Sampling frequency:

continuous

Operating principle: thermal conductivity (Liquid Sensor),  
float switch (Universal Sump Sensor, Universal Reservoir Sensor)

Test Results:

unleaded gasoline  

Liquid Sensor

 

Response time (min)

0.51

 

Recovery time (min)

<1

 

Product activation height (cm)

0.35

 

Lower detection limit (cm)

0.76

 

Universal Sump Sensor

 

 

Response time (min)

8.32

 

Recovery time (min)

<1

 

Product activation height (cm)

3.37

 

Lower detection limit (cm)

3.97

 

 

 

Universal Reservoir Sensor

 

50% by weight

ethylene glycol in water

 

30% by weight

calcium chloride in water

 

high*

low*

high

low

Response time (min)

19.62

16.86

17.77

15.91

Recovery time (min)

<1

<1

<1

<1

Product activation height (cm)

20.9

5.90

20.5

5.95

*The "high" and "low" refer to high and low level alarm points of hydrostatic sensors.

Specificity Results (in addition to above for Liquid Sensor and Universal Sump Sensor):
Activated:  diesel, synthetic gasoline, heating oil #2, water.

Comments:
Universal Reservoir Sensor is intended to monitor level of either ethylene glycol or calcium chloride solutions in the interstitial or annular space of a double-walled tank. 
Universal Reservoir Sensor activates an alarm if any significant gain or loss of solution occurs. 
Sensors are reusable.

 

OPW Fuel Management Systems

Evaluator:  Carnegie Mellon Research Institute

6900 Santa Fe Dr.

Tel:   (412) 268-3495

Hodgkins, IL 60525-9909

Date of Evaluation:  10/15/92

Tel:  (708) 485-4200

 

E-Mail:  info@opwfms.com  
URL:  www.opwfms.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.