Issue Date: June 1, 2001
Revision Date: December 4, 2008
OPW Fuel Management
Systems
(originally listed as Petro Vend, Inc.)
Site Sentinel
Models 1, 2 and 3, iTouch
(Model 924A
with 4 inch dia. Floats and 924B with
2 inch dia. or 4 inch dia. Floats, Magnetostrictive Probes)
AUTOMATIC TANK GAUGING METHOD
Certification |
Leak rate of 0.2
gph with PD = 97.8% and PFA = 2.2% for 30 minute test.
Leak rate of 0.2 gph with PD = 98.7% and PFA = 1.3% for 1 hour test.
Leak rate of 0.2 gph with PD = 99.2% and PFA = 0.8% for 2 hour test.
Leak rate of 0.2 gph with PD = 99.5% and PFA = 0.5% for 3 hour test.
Leak rate of 0.1 gph with PD = 96.9% and PFA = 1.9% for 2 hour test.
Leak rate of 0.1 gph with PD = 98.2% and PFA = 1.0% for 3 hour test. |
Leak
Threshold |
0.1 gph for leak
rate of 0.2 gph.
0.053 gph for leak rate of 0.1 gph.
A tank system should not be declared tight if the test result indicates a
loss or gain that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel. |
Tank
Capacity |
Maximum of 20,000
gallons.
Tank must be minimum 14% full for leak rate of 0.2 gph.
Minimum product level required based on 14% full tank and tank diameter is
as follows:
48" dia/min 9.5";
120" dia/min 24.7".
For other tank diameters, consult manufacturer.
Tank must be minimum 90% full for leak rate of 0.1 gph. |
Waiting
Time |
Minimum of 8
hours between delivery and testing for leak rate of 0.2 gph.
Minimum of 12 hours between delivery and testing for leak rate of 0.1
gph.
There must be no delivery during waiting time.
Minimum of 30 minutes between dispensing and testing. |
Test
Period |
Variable:
Minimum of 30 minutes, 1, 2 or 3 hours for leak rate of 0.2 gph and
minimum of 2 or 3 hours for leak rate of 0.1 gph.
Test data are acquired and recorded by system's computer.
Leak rate is calculated as the difference between the first and last data
collected.
There must be no dispensing or delivery during test. |
Temperature |
Average for
product is determined by a probe containing 5 thermistors with the lowest
thermistor located at the 10% tank volume level above the bottom of the
tank. |
Water
Sensor |
Must be used to
detect water ingress.
Minimum detectable water level in the tank is 0.848 inch.
Minimum detectable change in water level is 0.043 inch. |
Calibration |
Thermistors and
probe must be checked and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Comments |
Not evaluated
using manifolded tank systems. Therefore, this certification is only
applicable when there is a probe used in each tank and the siphon is broken
during testing.
Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to
lower head pressure).
Consistent testing at low levels could allow a leak to remain
undetected.
EPA leak detection regulations require testing of the portion of the tank
system which routinely contains product.
Site Sentinel models 2 and 3 were formerly models II and III respectively.
Model 924A Magnetostrictive Probe was formerly model 924.
Model 924B Magnetostrictive Probe is a newer probe that was not originally
listed under Petro Vend, Inc. |
OPW Fuel Management Systems
|
Evaluator:
Ken Wilcox Associates
|
6900 Santa Fe Dr.
|
Tel:
(816) 443-2494
|
Hodgkins, IL 60525-9909
|
Dates of
Evaluations: 11/03/00,
07/27/06
|
Tel: (708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|