| Issue Date: November 22, 1995Revision Date: September 18, 2007
 
 OPW Fuel Management 
Systems(originally listed as Petro Vend, Inc.)
 Site Sentinel
Models 2 and 3, (Model 613, 2 inch dia Floats, Magnetostrictive Probe)
 AUTOMATIC TANK GAUGING METHOD 
  
    | Certification | Leak rate of 0.2
      gph with PD = 96.55% and PFA = 3.45%. |  
    | Leak
      Threshold | 0.1 gph. A tank system should not be declared tight if the test result indicates a
      loss or gain that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuel. 
 |  
    | Tank
      Capacity | Maximum of 15,000
      gallons. Tank must be between 50 and 95% full.
 |  
    | Waiting
      Time | Minimum of 12
      hours between delivery and testing. There must be no delivery during waiting time.
 Minimum of 30 minutes between dispensing and testing.
 |  
    | Test
      Period | Minimum of 4
      hours. Test data are acquired and recorded by system's computer.
 Leak rate is calculated as the difference between the first and last data
      collected.
 There must be no dispensing or delivery during test.
 |  
    | Temperature | Average for
      product is determined by a minimum of 5 resistance temperature detectors (RTDs). |  
    | Water
      Sensor | Must be used to
      detect water ingress. Minimum detectable water level in the tank is 2.47 inches.
 Minimum detectable change in water level is 0.037 inch.
 |  
    | Calibration | RTDs and probe
      must be checked and, if necessary, calibrated in accordance with
      manufacturer's instructions. |  
    | Comments | Not evaluated 
    using manifolded tank systems. Therefore, this certification is only 
    applicable when there is a probe used in each tank and the siphon is broken 
    during testing. Tests only portion of tank containing product.
 As product level is lowered, leak rate in a leaking tank decreases (due to
      lower head pressure).
 Consistent testing at low levels could allow a leak to remain
      undetected.
 EPA leak detection regulations require testing of the portion of the tank
      system which routinely contains product.
 Site Sentinel models 2 and 3 were formerly models II and III respectively.
 |    
  
    | 