Issue Date: August 23, 1999
Revision Date: April 28, 2005

OPW Fuel Management Systems
(originally listed as Hasstech and later as Petro Vend, Inc.)

LineTight Pipeline Leak Monitor Model 2001J

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification

Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. 
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.

Leak Threshold 2.5 gph for leak rate of 3.0 gph. 
0.05 gph for leak rate of 0.1 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4.
Specification System tests pressurized fiberglass and steel pipelines. 
Tests are conducted at operating pressure. 
System will not function with a mechanical line leak detector installed in the pipeline.
Pipeline Capacity Maximum of 172 gallons.
Waiting Time None between delivery and testing. 
None between dispensing and testing.
Test Period Response time is 1 to 5 minutes for leak rate of 3.0 gph. 
Response time is 2 hours, 10 minutes for leak rate of 0.1 gph. 
Test data are acquired and recorded by a microprocessor. 
Calculations are automatically performed by the microprocessor.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. 
Preset threshold. 
Single test to determine if pipeline is leaking. 
Pump shutdown, message display, and alarm activation if leak is declared.
Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments Formerly manufactured by Hasstech

 

OPW Fuel Management Systems

Evaluator:  Ken Wilcox Associates

6900 Santa Fe Dr.

Tel:  (816) 443-2494

Hodgkins, IL 60525-9909

Dates of Evaluation:   04/15/97, 05/28/98

Tel:  (708) 485-4200

 

E-Mail:  info@opwfms.com  
URL:  www.opwfms.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.