| Issue Date: April 18, 1997Revision Date: 
April 28, 2005
 
 OPW Fuel Management 
Systems(originally listed as Hasstech and later as Petro Vend, Inc.)
 LineTite
Pipeline Leak Monitor(for Flexible Pipelines)
 AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR 
  
    | Certification | 
    Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA 
    = 0%.
 *Since leak 
    rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak
      Threshold | 2.0 gph for leak
      rate of 3.0 gph. 0.062 gph for leak rate of 0.1 gph.
 A pipeline system should not be declared tight if the test result
      indicates a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuel. |  
    | Specification | System tests 
    pressurized
      flexible pipelines. Tests are conducted at operating pressure.
 System will not function with a mechanical line leak detector installed on
      the pipeline.
 |  
    | Pipeline
      Capacity | Maximum of 49.6
      gallons. |  
    | Waiting
      Time | None between
      delivery and testing. None between dispensing and testing.
 |  
    | Test
      Period | Response time is
      1 to 6 minutes for leak rate of 3.0 gph. Response time is 2 hours, 18 minutes to 5 hours for leak rate of 0.1
      gph.
 Test data are acquired and recorded by a permanently installed
      microprocessor.
 Calculations are automatically performed by the microprocessor.
 |  
    | System
      Features | Permanent
      installation on pipeline. Automatic testing of pipeline.
 Preset threshold.
 Single test to determine if pipeline is leaking.
 Pump shutdown, message display, and alarm activation if leak is declared.
 |  
    | Calibration | System must be
      checked annually and, if necessary, calibrated in accordance with
      manufacturer's instructions. |  
    | Comments | Formerly
      manufactured by Hasstech |    
  
    | 
      OPW Fuel Management Systems | Evaluator: 
      Ken Wilcox Associates
      
      
       |  
    | 6900 Santa Fe Dr.
      
      
       | Tel: 
      (816) 443-2494
      
      
       |  
    | Hodgkins, IL 60525-9909
      
      
       | Dates of
      Evaluations:  10/15/91,
      04/10/94
      
       |  
    | Tel:  (708) 485-4200 
      
      
       |  
      
      
       |  
    | E-Mail:  
    info@opwfms.com |  |  