Issue Date: April 9, 2012
OPW Fuel Management Systems
iSite, iTouch, and EECO Series Fuel Management Systems with
OPW Intelligent Sensor (and Company Equivalent):
30-231-S, 30-0230-S (30-3221-1A/1B, Q003-009); 30-0231-L
(30-3221-1); 30-0232-D-10/D-20/D-10B/D-20B (Q0003-001/002); and the 924B Sump
Sensor
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
float
switch |
Test Results:
|
unleaded
gasoline
|
unleaded gasoline
|
unleaded gasoline
|
30-0231-S, 30-0230-S
|
E10 |
E15 |
E85 |
(30-3221-1A/1B, Q0003-0009) |
|
|
|
Lower detection limit (in) |
0.803 |
0.995 |
0.942 |
Detection time (min) |
<1 |
<1 |
<1 |
Fall time (min) |
<1 |
<1 |
<1 |
30-0231-L (30-3221-1) |
|
|
|
Lower detection limit (in) |
1.405 |
1.518 |
1.518 |
Detection time (min) |
<1 |
<1 |
<1 |
Fall time (min) |
<1 |
<1 |
<1 |
30-0232-D-10/D-20/D-10B/D-20B (Q0003-001/002) |
|
|
|
Lower detection limit (in) |
0.02 |
<0.125 |
<0.125 |
Detection time (min) |
<9 |
<13.72 |
<13.72 |
Fall time (min) |
<1 |
<1 |
<1 |
924B Sump Sensor |
|
|
|
Lower detection limit (in) |
4.029 |
4.029 |
4.029 |
Detection time (min) |
<1 |
<1 |
<1 |
Fall time (min) |
<1 |
<1 |
<1 |
Specificity
Results:
Evaluator claims sensors will
respond to any liquid.
Comments:
Manufacturer and evaluator claim sensors will
respond to any liquid after the sensor's threshold is exceeded.
OPW Fuel
Management Systems
|
Evaluator: Ken Wilcox
Associates
|
6900 Santa Fe Dr.
|
Tel: (816) 443-2494
|
Hodgkins, IL 60525-9909
|
Date of Evaluation:
5/31/11
|
Tel: (708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|