Issue Date: November 14, 1997
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO
1500, 2000, 3000, Leak Sensor, Leak Sensor II, Leak Sensor Jr.
with Q0002-001, Q00002-005 Sensors
OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
adsistor
(Q0002-001sensor), metal oxide semiconductor (Q0002-005 sensor) |
Test Results:
|
unleaded
gasoline
|
synthetic
gasoline
|
JP-4
jet fuel
|
Q0002-001 Sensor
|
|
|
|
Accuracy*
(%)
|
100
|
|
100
|
Detection
time* (min:sec)
|
19:32
|
|
09:16
|
Fall
time* (hh:mm:ss)
|
00:32:30
|
|
>01:05:33
|
Lower
detection limit (ppm)
|
1000
|
|
500
|
Q0002-005 Sensor
|
|
|
|
Accuracy*
(%)
|
100
|
100
|
100
|
Detection
time* (min:sec)
|
00:30
|
00:28
|
01:01
|
Fall
time* (min:sec)
|
03:34
|
02:40
|
05:33
|
Lower
detection limit (ppm)
|
100
|
100
|
100
|
*For
tests conducted with 1000 ppm of test gas.
**
See Glossary
Specificity Results (in addition to above):
Activated:
n-hexane, toluene, xylene(s).
Comments:
Q0002-001 sensor is not for use
with synthetic gasoline.
OPW Fuel
Management Systems
|
Evaluator: Carnegie Mellon
Research Institute
|
6900 Santa Fe Dr.
|
Tel: (412) 268-3495
|
Hodgkins, IL 60525
|
Date of Evaluations: 11/12/96,
10/18/96
|
Tel: (708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|