Issue Date: November 14, 1997
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO
1500, 2000, 3000 Systems
Q0003-001 Discriminating Dispenser
Pan Sensor, Q0003-002 Discriminating
STP Sump Sensor,
Q0003-003 Discriminating Interstitial
Sensor, Q0003-006 Liquid Only Interstitial Sensor,
Q0003-009 Liquid Float Sensor
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous
|
Operating
principle: |
float
switch and polymer strip (Q0003-001, Q0003-002), optical prism and
conductivity (Q0003-003), optical prism (Q0003-006), float switch
(Q0003-009) |
Test
Results:
|
unleaded
gasoline
|
diesel
|
water
|
Q0003-001
Discriminating
|
|
|
|
Dispenser Pan Sensor
(float switch, polymer strip)
|
high*
|
low*
|
high
|
low
|
high
|
low
|
Lower
detection limit (cm)
|
19.91
|
3.38
|
19.86
|
3.30
|
19.66
|
3.20
|
Detection
time (sec)
|
1-24hr
|
1-24hr
|
<1
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
clean
|
clean
|
clean
|
clean
|
<1
|
<1
|
Q0003-002
Discriminating STP Sump Sensor (float switch, polymer strip)
|
|
|
|
Lower
detection limit (cm)
|
28.37
|
3.12
|
28.24
|
3.07
|
28.04
|
3.00
|
Detection
time (sec)
|
1-24hr
|
1-24hr
|
<1
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
clean
|
clean
|
clean
|
clean
|
<1
|
<1
|
Q0003-003
Discriminating Interstitial Sensor (optical prism, conductivity)
|
|
|
|
Lower
detection limit (cm)
|
1.68
|
1.68
|
1.85
|
Detection
time (hr)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
Q0003-006
Liquid Only Interstitial Sensor (optical prism)
|
|
|
|
Lower
detection limit (cm)
|
1.35
|
1.55
|
1.78
|
Detection
time (hr)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
Q0003-009
Liquid Float Sensor
(float switch)
|
|
|
|
Lower
detection limit (cm)
|
2.54
|
2.49
|
2.21
|
Detection
time (hr)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
*The
"high" and "low" refer to high and low level alarm points of
hydrostatic sensors.
Specificity
Results:
Evaluator
claims sensors will respond to any liquid.
Comments:
Q0003-001
and Q0003-002 sensors must be cleaned with rubbing alcohol, or dish soap and
water after exposure to product.
Sensors
are reusable if not completely saturated with product.
OPW Fuel
Management Systems
|
Evaluator:
Ken Wilcox Associates
|
6900
Santa Fe Dr.
|
Tel: (816) 443-2494
|
Hodgkins,
IL 60525
|
Date of Evaluation:
10/18/96
|
Tel:
(708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|