Issue Date: November 22, 1995
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO
System, Leak Sensor II, Leak Sensor Jr.
Thermistor and Proximity probes
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
thermal
conductivity, proximity switch |
Test Results:
|
unleaded
gasoline
|
synthetic
gasoline
|
EECO System
|
|
|
Detection
time (sec)
|
<5
|
<5
|
Fall
time
|
manual
reset
|
manual
reset
|
Lower
detection limits (cm)
|
|
|
Thermistor
|
1.22
|
1.12
|
Proximity
|
0.97
|
1.04
|
Leak Sensor II
|
|
|
Detection
time (sec)
|
<5
|
<5
|
Fall
time
|
manual
reset
|
manual
reset
|
Lower
detection limits (cm)
|
|
|
Thermistor
|
1.14
|
1.14
|
Proximity
|
1.12
|
1.17
|
Leak Sensor Jr.
|
|
|
Detection
time (sec)
|
<5
|
<5
|
Fall
time
|
manual
reset
|
manual
reset
|
Lower
detection limits (cm)
|
|
|
Thermistor
|
1.24
|
1.19
|
Proximity
|
1.12
|
1.17
|
Specificity
Results (in addition to above):
Activated:
n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.
Comments:
Sensors are reusable.
Systems
alarm if either water or product leaks into interstitial space.
OPW Fuel Management Systems
|
Evaluator:
Ken Wilcox Associates
|
6900
Santa Fe Dr.
|
Tel: (816) 443-2494
|
Hodgkins, IL 60525
|
Date of Evaluation:
11/09/92
|
Tel:
(708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|