Issue Date: November 22, 1995
Revision Date:
April 28, 2005
OPW Fuel Management
Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO System
LLD (Q0011)
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
Certification |
Leak rate
of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
Leak
Threshold |
2.0 gph for leak
rate of 3.0 gph. 0.1293 gph for leak rate of 0.2 gph. 0.0793 gph for leak
rate of 0.1 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4. |
Specification |
System tests
pressurized fiberglass and steel pipelines.
Tests are conducted at operating pressure. |
Pipeline
Capacity |
Maximum of 67.4
gallons. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing for leak rate of 3.0 gph.
Ranges from 0 to 1 hour, 27 minutes between dispensing and testing for
leak rate of 0.2 gph.
Ranges from 0 to 2 hours, 48 minutes between dispensing and testing for
leak rate of 0.1 gph. |
Test
Period |
Response time is
2 minutes for leak rate of 3.0 gph.
Minimum of 9 minutes for leak rate of 0.2 gph.
Minimum of 31 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown, message display, and alarm activation if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
OPW Fuel
Management Systems
|
Evaluator:
Ken Wilcox Associates
|
6900
Santa Fe Dr.
|
Tel:
(816) 443-2494
|
Hodgkins, IL 60525
|
Date
of Evaluation: 12/31/93, 07/18/94
|
Tel:
(708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|