| Issue Date: June 22, 2012
 OPW Fuel Management 
Systems 
Model 327 VLLD Line Leak Detector 
(for Rigid, Flexible, or Hybrid Combination of 
Rigid and Flexible Pipelines) AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR 
  
    | Certification | Leak rate 
    of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
 Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 97.9% and PFA 
    = 2.1%.
 *Since leak 
    rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak
      Threshold | 1.5 gph for leak
      rate of 3.0 gph.  0.1 gph for leak rate of 0.2 gph. 
	 0.05 gph for leak
      rate of 0.1 gph. A pipeline system should not be declared tight if the test result
      indicates a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 
	meeting ASTM D7467, biodiesel B100 meeting ASTM D6751.   |  
    | Specification | System tests
      pressurized rigid or flexible or a combination of rigid and flexible pipelines 
	for all leak rates.. Tests are conducted at operating pressure.
 |  
    | Pipeline
      Capacity | For all leak rates 
	3.0 gph, 0.2 gph and 0.1 gph:   Maximum of 
	425.8 gallons for rigid pipelines.   Maximum of 
	109.8 gallons for flexible pipelines.   Maximum 
	combined capacity is 535.7 gallons, not to exceed the above individual 
	capacity limitations for rigid or flexible pipelines. |  
    | Waiting
      Time | None between
      delivery and testing. None between dispensing and testing for all leak rate 3.0 gph, 0.2 gph and 
	0.1 gph.
 |  
    | Test
      Period | Response time is
      3 minutes or less for leak rate of 3.0 gph. Minimum of 204 minutes for leak rate of 0.2 gph.
 Minimum of 204 minutes for leak rate of 0.1 gph.
 Test data are acquired and recorded by a microprocessor.
 |  
    | System
      Features | Permanent
      installation on pipeline. Automatic testing of pipeline every 45 minutes for leak rate of 3.0 gph.
 Automatic testing 
	of pipeline for leak rate of 0.2 gph based upon thermal condition. Automatic testing 
	of pipeline for leak rate of 0.1 gph based upon thermal conditions. Preset threshold.
 Single test to determine if pipeline is leaking.
 Pump shutdown, indicator light, and alarm activation if leak is declared.
 |  
    | Calibration | System must be
      checked annually and, if necessary, calibrated in accordance with
      manufacturer's instructions. |    
  
    | 
      OPW Fuel 
      Management Systems | Evaluator: 
      Ken Wilcox Associates
      
      
       |  
    | 
      6900 
      Santa Fe Dr. | Tel: 
      (816) 443-2494
      
       |  
    | 
      Hodgkins, IL 60525
      
      
       | Date
      of Evaluation:  03/26/12
      
      
       |  
    | 
      Tel: 
      (708) 485-4200 |  
      
       |  