Issue Date: November 22, 1995
Revision Date: April 18, 1997

One Plus Corp.

Leak Edge 
Models 100-3001, 100-4001

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

Detection time (min:sec)

5:41

5:14

Fall time (min:sec)

30:39

18:36

Lower detection limit (cm)

0.02

0.02

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Manufacturer’s specifications:
Operating temperatures: Sensor is -40 degrees C to 74 degrees C; Monitor Module is -20 degrees C to 49 degrees C.

Comments:
Sensors are reusable.

 

One Plus Corp.               

Evaluator:  Underwriters Laboratories Inc.

3182 McArthur Blvd.

Tel:  (847) 272-8800

Northbrook, IL 60062

Date of Evaluation:  12/17/91

Tel:  (847) 498-0955

 

 