Issue Date: January 6, 2022
OMNTEC MFG., INC.
OMNTEC OEL8000III-CLD PORTABLE CONTAINMENT SUMP TESTER (CLD SERIES)
SECONDARY CONTAINMENT SUMP TEST METHOD
Certification | .1 GPH with PD =
100% and PFA = 0% Please be aware that the authority having jurisdiction in your particular state, territory, tribe or municipality may have set a minimum detectable leak rate for Secondary and Spill Containment Test Methods. |
Leak Threshold | 0.0020 inch/15 minutes (0.008 inch/hour) |
Applicability |
Water |
Specification | System tests wetted portion of turbine, transition and dispenser containment sumps |
Waiting Time | Water level readings must stabilize (due to distortion of sumps and wave action) and temperature in sump must stabilize prior to beginning test. |
Test Period | 15 minutes |
System Features | Up to 8 sumps can be tested at the same time |
Calibration | No calibration is required |
Comments | Adaptable to the requirements of PEI/RP-1200-17. Has programmable leak threshold and duration that can be adjusted appropriately for any size containment sump. Default test leak threshold/duration setting is 0.002 inches/15 minutes. Equipment only tests portions of the sump that contains test fluid. |
OMNTEC Mfg., Inc. |
Evaluator: Ken Wilcox Associates |
2420 Pond Rd. |
Tel: (816) 443-2494 |
Ronkonkoma, NY 11779 |
Date of Evaluation: 07/20/21 |
Tel:(631) 981-2001 |
|
Website: www.omntec.com | |
Email: omntec@omntec.com |
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |
Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations. For full details, please refer to our expanded "DISCLAIMER"
page.