Issue
Date: November 7,
2001
OMNTEC
Mfg., Inc.
Controller
Models OEL 8000 11, K-OEL 8000 11 with
Liquid level sensors BX-PDS, BX-PDWF, BX-PDWS
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative,
discriminating |
Sampling
frequency: |
continuous |
Operating
principle: |
optical
sensor, conductivity |
Test
Results:
|
unleaded
gasoline
|
diesel
|
water
|
BX-PDS
|
|
|
|
Detection time (sec)
|
< 1
|
< 1
|
< 1
|
Fall time (sec)
|
< 1
|
< 1
|
< 1
|
Lower detection limit (cm)
|
0.464
|
0.468
|
0.500
|
BX-PDWF
|
|
|
|
Detection time (sec)
|
< 1
|
< 1
|
< 1
|
Fall time (sec)
|
< 1
|
< 1
|
< 1
|
Lower detection limit (cm)
|
0.63
|
0.46
|
0.40
|
BX-PDWS
|
|
|
|
Detection time (sec)
|
< 1
|
< 1
|
< 1
|
Fall time (sec)
|
< 1
|
< 1
|
< 1
|
Lower detection limit (cm)
|
0.464
|
0.468
|
0.500
|
Specificity
Results:
Manufacturer claims sensors will
respond to any liquid after its threshold is exceeded.
No additional materials tested.
Manufacturer’s
Specifications:
Manufacturer states that the
sensors can also be tested from their location without removal.
The test procedure is as follows: When the test button on the controller is
pressed, the normally closed light beam is opened, which simulates an actual
leak occurrence, sending an alarm signal to the controller.
The controller responds to the alarm signal by turning on an audio/visual
alarm and printing the test results.
Comments:
Optic
sensor BX-PDS also contains a conductivity sensor to determine if the product is
hydrocarbon or water.
OMNTEC
Mfg., Inc.
|
Evaluator:
Ken Wilcox Associates
|
1993 Pond Rd.
|
Tel:
(816) 443-2494
|
Ronkonkoma, NY
11779
|
Dates
of Evaluation: 11/15/00
|
Tel: (631) 981-2001
|
|
|