Issue Date: June 4, 2003
Revision Date: April 28, 2005
MassTech
International, Ltd.
MassTech Analog Acoustic Vacuum Method
(Vacuum Test)
NON-VOLUMETRIC TANK TIGHTNESS
TEST METHOD (ULLAGE)
Certification |
Leak rate of 0.1
gph with PD = 96.2% and PFA = 0%. |
Leak Threshold |
Tank ullage
should not be declared tight when the acoustic signal characteristic of a
leak is detected. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4, waste oil. Empty tanks may also be tested.
Product-filled portion of the tank must be tested using an underfill test
method.
|
Tank Capacity |
Maximum ullage
volume is 20,000 gallons. |
Waiting Time |
None between
delivery and testing. |
Test Period |
Minimum of 2
minutes.
There must be no dispensing or delivery during test. |
Test Pressure |
A nominal vacuum
of 1.5 psig must be maintained in the ullage. |
Temperature |
Acoustic signal
is independent of product temperature. |
Groundwater |
Depth to
groundwater in tank excavation backfill must be determined.
If groundwater or other liquid is present outside tank ullage, test must not
be used. |
Comments |
Microphone
(hydrophone) should be located within 25 feet of any possible leak source.
Noise signals are tape recorded (not digitally recorded) so that test data
can be reviewed by the test operator or other qualified individuals.
Since the
method depends on an audible interpretation of the signal, the test must be
conducted under reasonably quiet conditions.
Vibrations due to heavy traffic, nearby trains, or construction activities
could produce sound levels that could compromise the test.
Vacuum test method may not be effective in some tank excavation backfill
(such as clay) because it may plug holes in tank.
If free product is present in tank excavation backfill, a leak in the free
product zone may not be detected by a vacuum test method.
A well point or observation well in the tank excavation backfill may help
determine backfill material, water level in tank excavation backfill, and
free product.
Operators must be trained and certified by the manufacturer. |
MassTech
International, Ltd. |
Evaluator: Ken Wilcox
Associates, Inc. |
102 Basile Road |
Tel: (816) 443-2494 |
Scott, LA 70583 |
Date of Evaluation:
01/02/01 |
Tel: (337) 896-8230 |
|
E-mail: masstech1@compuserve.com |
|
URL: