 Leighton 
O'Brien Technologies, 
Ltd. 
Qualitative Dry Line Test PM2 (for Rigid and Flexible 
Pipelines) 
LINE TIGHTNESS TEST 
METHOD 
  
    | 
    Certification | Leak 
    rate of 0.1 gph with PD = 100% and PFA = 0%.Leak rate of 0.025 gph with PD = 100% and PFA = 0%.
 
 |  
    | 
    Leak Threshold | < 0.05 
    gph.  Proprietary for dry test mode.< 0.0125 gph for leak rate of 0.025 gph.
 |  
    | 
    Applicability | 
    Any dry pipeline. |  
    | 
    Specification | System tests fiberglass, steel and flexible pipelines.  Dry Tests are conducted at 45 psi or 150% of operating pressure using the system as a digital manometer against the fluid and trapped vapor in the pipeline.
 Mechanical line leak detector must be removed or manually isolated from pipeline for duration of test, or if testing is to be conducted with mechanical line leak detector in place, check valve in pump must be manually closed.
 |  
    | 
    Pipeline Capacity | For leak rate of 0.1 gph Maximum of 371.22 gallons in rigid piping.
 Maximum of 109.8 gallons in flexible piping.
 Maximum total of 481 gallons in combination rigid and flexible (the capacity of the flexible component cannot exceed 109.8 gallons).
 Manifolded piping may be tested as long as the total length of piping is within the capacity and configuration limitations.
 
 For leak rate of 0.025 gph
 Maximum of 165 gallons in rigid piping.
 Maximum of 110 gallons in flexible piping.
 Maximum total of 275 gallons in combination rigid and flexible (the capacity of the flexible component cannot exceed 110 gallons).
 Maximum pipe diameter is 6.00 inches.
 Manifolded piping may be tested as long as the total length of piping is within the capacity and configuration limitations.
 
 |  
    | 
    Waiting Time | None 
    between delivery and testing. None between dispensing and testing.
 |  
    | 
    Test Period | 
	For leak rate of 0.1 gph  Minimum of 3 minutes after installing in line.
 Test data is collected continuously and recorded by computer.
 Data is analyzed at the Leighton O'Brien analysis center with telemetry.
 
 For leak rate of 0.025 gph
 Minimum of 5 minutes after installing in line.
 Test data is collected continuously and recorded by computer.
 Data is analyzed at the Leighton O'Brien analysis center with telemetry.
 |  
    | 
    Calibration | 
	No temperature sensors used. 
	System must be calibrated 
	yearly in accordance with manufacturer's instructions. |  
    | 
    Comments | 
	Groundwater is overcome with pressure on the top of the fluid test system 
	apparatus during the dry test. |    
  
    
      | Leighton O'Brien 
		Technologies, Ltd. | Evaluator: 
      Ken Wilcox Associates |  
      | Suite 1/96 Camberwell Road | Tel: 
      (816) 443-2494 |  
      | Hawthorn East, Victoria, 
		Australia 3123 | Date of Evaluation: 
      10/11/10, 06/21/2018 |  
      | Tel:  +61(03) 
		9813 5122 |  |  
      | E-mail: enquiry@leightonobrien.com |  |  
      | URL: http://www.leightonobrien.com |  |    |