Issue Date: April 18, 1997
Revision Date: March 3, 2009
Horner
Products, Inc.
SIR PRO 1
Version 4.0
STATISTICAL INVENTORY
RECONCILIATION TEST METHOD (QUANTITATIVE)
Horner Products is no longer in business.
Support for this method may not be available.
Certification |
Leak rate of 0.1
gph with PD = 98% and PFA = 2%. |
Leak
Threshold |
0.05 gph.
A tank system should not be declared tight if the test result indicates a
loss or gain that equals or exceeds this threshold. |
Applicability |
Gasoline,
diesel.
|
Tank
Capacity |
Maximum of 33,000
gallons for single tanks.
Size limits using an acceptable protocol for manifolded tank systems have
not been determined. |
Data
Requirement |
Minimum of 30
days of product level and flow through data. |
Comments |
Not evaluated for
manifolded tank systems using an acceptable protocol.
73% of data sets were from manifolded tank systems.
Of 41 data sets submitted for evaluation, 4 were inconclusive.
Median monthly throughput of tanks evaluated was 22,370 gallons.
Leak rates ranging from 0.05 to 0.216 gph were used in evaluation.
Data sets evaluated were supplied by evaluator. |
Manufacturer's Previously Listed Contact
|
Evaluator: Ken
Wilcox Associates
|
Information is No Longer Valid
|
Tel: (816) 443-2494
|
|
Date of Evaluation: 07/18/95
|
|
|
|