Issue Date: April 18, 1997
Revision Date: May 23, 2011
 

Hasstech

Tank Compliance Center, Model 700
(7100 Series Magnetostrictive Probe)

AUTOMATIC TANK GAUGING METHOD

Hasstech is no longer in business.

Certification Leak rate of 0.2 gph with PD = 99.9% and PFA = 0.1%. 
Leak Threshold 0.1 gph for leak rate of 0.2 gph.
A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4. 
Tank Capacity Maximum of 15,000 gallons. Tank must be between 50 and 95% full.
Waiting Time Minimum of 2 hours between delivery and testing. Minimum of 2 hours between dispensing and testing. 
There must be no delivery during waiting time.
Test Period Minimum of 2 hours for leak rate of 0.2 gph. 
Test data are acquired and recorded by system's computer. 
Leak rate is calculated from data determined to be valid by statistical analysis. 
There must be no dispensing or delivery during test.
Temperature Average for product is determined by a minimum of 5 thermistors.
Water Sensor Must be used to detect water ingress. 
Minimum detectable water level in the tank is 0.186 inch. 
Minimum detectable change in water level is 0.0048 inch.
Calibration Thermistors and probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments Not evaluated using manifolded tank systems. Therefore, this certification is only applicable when there is a probe used in each tank and the siphon is broken during testing. 
Tests only portion of tank containing product. 
As product level is lowered, leak rate in a leaking tank decreases (due to lower head pressure). 
Consistent testing at low levels could allow a leak to remain undetected. 
EPA leak detection regulations require testing of the portion of the tank system which routinely contains product. System no longer being manufactured and no support is available.

 

Hasstech

Evaluator:  Ken Wilcox Associates

out of business

Tel:  (816) 443-2494

 

Date of Evaluation:  03/14/95

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.