Issue Date: November 22, 1995
Revision Date: June 5, 2002
 

Gems Sensors, Inc.
(originally listed as Warrick Controls, Inc.)

Model 5700 Meter with PVP-2 Sensor

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:

Output type:

quantitative

Sampling frequency:

continuous

Operating principle:

adsistor

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

JP-4 jet fuel

Accuracy (%)

25.4

-100.0

157.1

Bias (%)

14.4

-100.0

108.3

Precision (%)

7.6

N/D*

20.4

Detection time (min)

>60

N/A*

>60

Fall time (min)

38

N/A

>60

Lower detection limit (ppm)

1353.3

N/D

N/D

* See glossary.

Specificity Results:
Not Activated:  n-hexane, toluene, xylene(s).

 