Issue Date: April 18, 1997
Revision Date: June 5, 2002
 

Gems Sensors, Inc.
(originally listed as Warrick Controls, Inc.)

Model DFP-25 Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:               qualitative

Sampling frequency:    continuous

Operating principle:     product solubility

 

Test Results:

 

 

unleaded gasoline

diesel

water

Detection time (hr:min:sec)

0:06:50

4:14:40

N/A

Fall time**

N/A*

N/A

N/A

Lower detection limit (cm)

2.54

2.54

N/A

* See glossary.
**Fall time is not applicable, since sensor must be replaced after activating.

Specificity Results:
Activated:  Evaluator claims that this sensor will respond to any material that is capable of dissolving the hydrocarbon-sensitive wax.
Not Activated:  Water.

Comments:
Sensor is activated when hydrocarbon-sensitive wax is dissolved, releasing a spring that activates an alarm.
Sensor is not reusable, and must be replaced after contact with hydrocarbons.
Liquid level was set at 1 inch (2.54 cm) during test.

 

Gems Sensors, Inc.

Evaluator:  Ken Wilcox Associates

1 Cowles Rd.

Tel:  (816) 443-2494

Plainville, CT 06062-1198

Date of Evaluation:  11/18/96

Tel: (800) 378-1600

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.