Issue Date: April
18, 1997
Revision Date: June 5, 2002
Gems
Sensors, Inc.
(originally listed as Warrick Controls, Inc.)
Model DFP-25 Sensor
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
Output type:
qualitative
Sampling
frequency: continuous
Operating
principle: product solubility
Test Results:
|
unleaded gasoline |
diesel |
water |
Detection time (hr:min:sec) |
0:06:50 |
4:14:40 |
N/A |
Fall
time** |
N/A* |
N/A |
N/A |
Lower
detection limit (cm) |
2.54 |
2.54 |
N/A |
*
See glossary.
**Fall time is not applicable, since sensor must be replaced after activating.
Specificity Results:
Activated: Evaluator claims that
this sensor will respond to any material that is capable of dissolving the
hydrocarbon-sensitive wax.
Not Activated:
Water.
Comments:
Sensor is activated when
hydrocarbon-sensitive wax is dissolved, releasing a spring that activates an
alarm.
Sensor is not reusable, and must be replaced after contact with hydrocarbons.
Liquid level was set at 1 inch (2.54 cm) during test.
Gems
Sensors, Inc. |
Evaluator: Ken Wilcox Associates |
1 Cowles
Rd. |
Tel:
(816) 443-2494 |
Plainville, CT 06062-1198 |
Date of
Evaluation: 11/18/96 |
Tel:
(800) 378-1600 |
|
|