Issue Date: August 06, 2020
Franklin Fueling Systems
EVO 600 and EVO 6000 Consoles with TSP-HIS BriteSensor and TSP-HIS-XL Sensor
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector: |
|
Output Type: |
qualitative |
Sampling Frequency: |
continuous |
Operating principle: |
magnetic switch |
Test Results:
|
|
brine |
|
|
|
|
|
TSP-HIS BriteSensor |
high* |
low* |
|
Detection time (min) |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
|
Product activation height (in) |
7.8099 |
1.0631 |
|
|
|
|
|
|
|
|
|
TSP-HIS-XL |
high* |
low* |
|
Detection time (min) |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
|
Threshold Level |
10.9546 |
1.00061 |
|
|
|
|
|
|
*The "high" and "low" refer to high- and low-level alarm points of hydrostatic sensors.
Comments:
TSP-HIS BriteSensor is intended to monitor level of either ethylene glycol or calcium chloride solutions in interstitial or annular space of a double-walled tank. Activates if any significant gain or loss of solution occurs.
Sensors are reusable. |
Franklin
Fueling Systems |
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road |
Tel: (816)
443-2494 |
Madison, WI
53718 |
Dates of
Evaluations: 12/17/2018 |
Tel: (800)
225-9787 |
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com |
|
|