Issue Date: August 6, 2020
Franklin Fueling Systems
(originally listed as INCON Intelligent Controls, Inc.)
EVO 600 and EVO 6000 Consoles with TSP-HFS Horizontal Float, TSP-HLS Standard Sensor,
TSP-ULS, and TSP-UHS Standard Sensors Switch
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector: |
|
Output Type: |
qualitative |
Sampling Frequency: |
continuous |
Operating principle:
|
magnetic switch
|
Test Results:
|
|
unleaded gasoline |
diesel* |
E85 |
water
|
|
TSP-HFS Standard Sensor |
|
|
|
|
|
Detection time (min:sec) |
<1 |
<1 |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
|
Product activation height (in) |
0.5146 |
0.4908 |
0.5046 |
0.4480 |
|
TSP-HLS Standard Sensor |
|
|
|
|
|
Detection time (min:sec) |
10:09 |
09:55 |
<1 |
09:25 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
|
Product activation height (in) |
2.0328 |
1.9408 |
2.0030 |
1.7658 |
|
TSP-ULS Standard Sensor |
|
|
|
|
|
Detection time (min:sec) |
03:50 |
03:50 |
03:41 |
03:34 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
|
Product activation height (in) |
1.1243 |
1.0726 |
1.0994 |
0.9529 |
|
TSP-UHS Standard Sensor |
|
|
|
|
|
Detection time (min:sec) |
03:50 |
03:50 |
<1 |
03:34 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
|
Product activation height (in) |
0.9628 |
0.8966 |
0.9125 |
0.7952 |
|
|
*This evaluation determined the sensor's responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined but would be expected to be very similar to the diesel responses.
Comments:
Ken Wilcox Associates (KWA) has previously evaluated these sensors on one or more Franklin Fueling Systems ATG consoles. Results from the alarm functionality testing with the EVO600 and EVO6000 consoles has been combined with previously evaluated sensor threshold data performed by KWA, as well as Carnegie Mellon Research Institute.
TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor.
Sensors are reusable. |
Franklin
Fueling Systems
|
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road
|
Tel: (816)
443-2494
|
Madison, WI
53718
|
Dates of
Evaluations: 12/17/18
|
Tel: (800)
225-9787
|
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com
|
|
|