Issue Date: August 07, 2017
Franklin Fueling Systems
Franklin Fueling Systems EVO400, EVO200 with
FMP-HIS-U Hydrostatic Interstitial Float Sensor, and FMP-HIS-XL-U Hydrostatic Interstitial Float
Sensor
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector: |
|
Output Type: |
qualitative |
Sampling Frequency: |
continuous |
Operating principle: |
float switch |
Test Results:
|
|
brine |
|
|
|
|
|
|
FMP-HIS |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
|
|
|
|
|
|
Fall time (min) |
<1 |
|
|
|
|
|
|
Threshold Level |
|
|
|
|
|
|
|
Low level (in) |
1.0167 |
|
|
|
|
|
|
High level (in) |
7.3218 |
|
|
|
|
|
|
FMP-HIS-XL |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
|
|
|
|
|
|
Fall time (min) |
<1 |
|
|
|
|
|
|
Threshold Level |
|
|
|
|
|
|
|
Low level (in) |
0.9895 |
|
|
|
|
|
|
High level (in) |
10.8398 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Manufacturer and evaluator claim that sensors will respond to any liquid. Evaluations determined these sensors' responses to the liquids shown above. *Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments:
Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested. |
Franklin
Fueling Systems |
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road |
Tel: (816)
443-2494 |
Madison, WI
53718 |
Dates of
Evaluations: 06/19/2017 |
Tel: (800)
225-9787 |
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com |
|
|