Issue Date: August 07, 2017
Franklin Fueling Systems
Incon TS-1001/2001, TS-5, TS-550, TS-5000, TS-550 evo, TS-5000 evo, EVO400, EVO200,
and S940 Alarm Console with FMP-ULS Universal Liquid Sensor, FMP-UHS Universal
Hydrostatic Sensor, FMP-ULS-C Universal Liquid Sensor Chemical, FMP-ULS-PS Universal
Liquid Sensor Position Sensitive sensors
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector: |
|
Output Type: |
qualitative |
Sampling Frequency: |
continuous |
Operating principle: |
float/reed switch |
Test Results:
|
|
unleaded gasoline |
Diesel* |
Biodiesel*
|
Water
|
E85
|
Brine
|
|
FMP-ULS |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
|
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
|
|
Threshold Level (in) |
1.0155 |
0.9944 |
0.9925 |
0.8775 |
1.0198 |
|
|
FMP-UHS |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
|
Threshold Level (in) |
0.9602 |
0.9144 |
0.9218 |
0.9397 |
0.9397 |
0.7561 |
|
FMP-ULS-PS |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
|
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
<1 |
|
|
Threshold Level (in) |
1.4915 |
1.4882 |
1.4758 |
1.3770 |
1.4962 |
|
|
|
|
|
|
|
|
|
|
|
Lubrizol** |
Afton** |
|
|
|
|
|
FMP-ULS-C |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
|
|
|
|
|
Fall time (min) |
<1 |
<1 |
|
|
|
|
|
Threshold Level (in) |
1.1707 |
1.1281 |
|
|
|
|
|
FMP-ULS-PS |
|
|
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
|
|
|
|
|
Fall time (min) |
<1 |
<1 |
|
|
|
|
|
Threshold Level (in) |
1.4959 |
1.4290 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Evaluations determined these sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
** Manufacturer and evaluator claim that responses to Lubrizol 9888 and 9888C would be expected to be very similar to each other. Responses to Afton OTR 8332G. and OTR 8843G would be expected to be very similar to each other.
Comments:
Sensor TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor. The FMP-ULS-PS is a position sensitive float switch that issues an alarm if not installed properly at the bottom of the intestinal or sump.
Sensors are reusable. |
Franklin
Fueling Systems |
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road |
Tel: (816)
443-2494 |
Madison, WI
53718 |
Dates of
Evaluations: 05/02/2017 |
Tel: (800)
225-9787 |
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com |
|
|