Issue Date: February
11, 2009
Revision Date:
December 30, 2010
Franklin Fueling Systems
Tank
Sentinel TS-5xxx Series with TSP-DMS 12 and 24 Inch Discriminating
Magnetostrictive Sensors
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector: |
|
Output Type:
Sampling Frequency:
Operating principle: |
qualitative
continuous
magnetostrictive probe with dual floats |
Test Results:
|
TSP-DMS 12 Inch and 24 Inch
Discriminating Sensor |
unleaded gasoline |
diesel* |
water
|
|
Detection time (min) |
<1 |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
<1 |
|
Average product activation height (in) |
1.97 |
1.86 |
1.54 |
|
Minimum detectable level (in) |
1.98 |
1.87 |
1.55 |
|
|
*This evaluation determined the sensor's responses to the liquids shown
above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100
meeting ASTM D6751 would also produce an alarm if the sensor threshold is
exceeded. Responses to these fuels were not determined, but would be
expected to be very similar to the diesel responses.
Comments:
These sensors were evaluated for use with
the TS-5xxx series consoles only.
Sensors are reusable.
|
Franklin
Fueling Systems
|
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road
|
Tel: (816)
443-2494
|
Madison, WI
53718
|
Dates of
Evaluations: 07/16/2008
|
Tel: (800)
225-9787
|
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com
|
|
|