Issue Date:
September 1, 2006
Revision Date: April 11, 2016
Franklin
Fueling Systems
TS-LS500,
TS-LS500E
Series
(for Rigid, Flexible or Hybrid Combination of Rigid and Flexible Pipelines)
AUTOMATIC
ELECTRONIC LINE LEAK DETECTOR
Certification |
Leak
rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak rate varies as a function of pressure, this leak rate and
pressure were certified using an equivalent leak rate and pressure, in
accordance with an acceptable protocol. |
Leak Threshold |
1.5
gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel, aviation fuels, fuel oil #4, waste oil, kerosene,
biodiesel B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751.
|
Specification |
On pressurized rigid, flexible, or combination
rigid and flexible pipelines, system can perform 3.0 gph, 0.2 gph, and 0.1
gph tests.
Tests are conducted at operating pressure. |
Pipeline Capacity |
Maximum of 312.2 gallons for steel and fiberglass pipelines (examples: 480
feet of 4 inch line; 671 feet of 3 3/8 inch line ).
Maximum of 95.4 gallons for flexible pipelines (examples: 260 feet of 3 inch
line; 1040 feet of 1 ½ inch line).
Maximum of 415.8 gallons for hybrid combination of rigid and flexible pipelines (the
capacity of the flexible component cannot exceed 95.4 gallons).
Maximum of 176 gallons for Franklin Fueling Systems UPP semi-rigid pipeline. (example: 513 feet of 3 inch line; 1892 feet of 1 1/2 inch line). |
Waiting Time |
None
between delivery and testing.
None between dispensing and testing for leak rate of 3.0 gph.
Depending on temperature stability, 1½ to 10 hours between dispensing and
testing for leak rates of 0.2 gph and 0.1 gph. |
Test Period |
Response time is 1 to 2 minutes for leak rate of 3.0 gph.
Minimum of 25 minutes for leak rate of 0.2 gph.
Minimum of 34 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor. |
System Features |
Permanent installation on pipeline.
Automatic testing of pipeline every 45 minutes for leak rate of 3.0 gph.
Automatic testing of pipeline when pump has been idle for 2 hours for leak
rate of 0.2 gph.
Automatic testing of pipeline when pump has been idle for 3½ hours for leak
rate of 0.1 gph.
Pump shutdown, indicator light and alarm activation if leak is declared for
3.0 gph and 0.2 gph tests.
The TS-LS500E series is an explosion proof version of the original TS-LS500
series. |
Calibration |
System
must be checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Franklin
Fueling Systems
|
Evaluator:
Ken Wilcox Associates
|
3760 Marsh Road
|
Tel:
(816) 443-2494
|
Madison, WI
53718
|
Dates of
Evaluations: 06/23/95, 09/10/98, 02/28/06, 8/28/06, 01/10/08, 01/20/16
|
Tel: (800)
225-9787
|
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com
|
|
|