Issue Date: May 8, 2012
Revision Date: June 16, 2014
Franklin Fueling Systems
FE PETRO STP-MLD+G, STP-MLD+AG, STP-MLD+D and
STP-MLD+BD Pipeline Leak Detector
(for Rigid, Flexible, or Hybrid
Combination of Rigid and Flexible Pipelines)
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak
Threshold |
3.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline,
gasoline-alcohol mixtures, aviation fuel, fuel oil #4, solvents, diesel,
biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM
D6751.
|
Specification |
System tests
pressurized rigid and flexible pipelines.
Tests are conducted at operating pressure. |
Pipeline
Capacity |
Maximum for rigid system is 165.1
gallons.
Maximum for
flexible system is 109.8
gallons.
Maximum combined capacity is 274.9 gallons, not to exceed the
above individual capacity limitations for rigid or flexible pipelines. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing. |
Test
Period |
Response time is
less than 2 minutes. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline. Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Franklin Fueling Systems
|
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road
|
Tel: (816) 443-2494
|
Madison, WI
53718
|
Date of Evaluation:
03/16/12, 3/19/14
|
Tel: (800)
225-9787
|
|
E-mail: info@franklinfueling.com |
|
URL: www.franklinfueling.com |
|
|