Issue Date: April 18, 1997Revision Date: June 20, 2008
 
Franklin Fueling Systems(originally listed as INCON Intelligent Controls, Inc.)
 
Tank Sentinel TS-1000EFI, TS-1001/TS-2001, and 
TS-5xxx Series withTSP-DDS BriteSensor, TSP-DTS BriteSensor, TSP-MWS BriteSensor Groundwater Probe
 
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE) Detector: 
  
    | Output
      type: | qualitative |  
    | Sampling
      frequency: | continuous |  
    | Operating
      principle: | magnetic
      switch and float (TSP-DDS, TSP-DTS BriteSensor), and hydrocarbon sensitive
      polymer (all) |    Test Results: 
  
    |  | unleaded
      gasoline
      
       | synthetic
      gasoline
      
       |  
      
       diesel
      
       | heating
      oil #2
      
       | water
      
      low
      level
 | water high level
 |  
    |  
      
      TSP-DDS
      BriteSensor
      
       |  |  |  |  |  |  |  
    | Detection
      time (min:sec)
      
       | 05:35
      
       | 06:00
      
       | 38:43
      
       | 38:16
      
       | 06:02
      
       | 06:09
      
       |  
    | Fall
      time (min:sec)
      
       | 34:27
      
       | 28:53
      
       | >
      60:00
      
       | >
      60:00
      
       | <01:00
      
       | <01:00
      
       |  
    | Lower
      detection limits (cm)
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
    |     
      Product activation height 
      
       | 0.50
      
       | N/D*
      
       | 3.16
      
       | N/D
      
       | N/D
      
       | N/D
      
       |  
    |     
      Product thickness on water 
      
       | 0.04
      
       | N/D
      
       | N/D
      
       | N/D
      
       | N/D
      
       | N/D
      
       |  
    | TSP-DTS
      BriteSensor
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
    | Detection
      time (min:sec)
      
       | 06:02
      
       | 05:59
      
       | 38:43
      
       | 38:16
      
       | 06:02
      
       | 06:13
      
       |  
    | Fall
      time (min:sec)
      
       | 22:28
      
       | 28:53
      
       | <01:00
      
       | <01:00
      
       | >
      60:00
      
       | >
      60:00
      
       |  
    | Lower
      detection limits (cm)
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
      
       |  
    |     
      Product activation height 
      
       | 0.50
      
       | N/D
      
       | 3.16
      
       | N/D
      
       | N/D
      
       | N/D
      
       |  
    |     
      Product thickness on water 
      
       | 0.04
      
       | N/D
      
       | N/D
      
       | N/D
      
       | N/D
      
       | N/D
      
       |  
    | TSP-MWS
      BriteSensor Groundwater Probe
      
       |  
      
       |  
      
       |   |  
    | Detection
      time (min:sec)
      
       | 10:13
      
       | 06:42
      
       |   |  
    | Fall
      time (min:sec)
      
       | 26:52
      
       | 14:43
      
       |   |  
    | Lower
      detection limit (cm)
      
       |  
      
       |  
      
       |   |  
    |     
      Product thickness on water
      
       | 0.04
      
       | 0.04
      
       |   |  *
See glossary. Specificity
Results (additional for TSP-MWS BriteSensor Groundwater Probe):Activated: 
n-hexane, diesel, jet-A fuel, toluene, xylene(s).
 Comments:Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles 
with Tank Sentinel TS-1000(including EFI)//TS-2000 series consoles showed 
comparable results when evaluated with representative sensors.
 Sensors
are reusable.
   
  
    | 
      Franklin Fueling Systems | Evaluator: Carnegie Mellon Research Institute
      
      
       |  
    | 3760 Marsh Road | Tel:  (412) 268-3495 |  
    | 
      Madison, WI  53718 | Dates of Evaluations: 
      
      
      12/09/94,
      02/19/96 |  
    | 
      Tel:  (800) 225-9787 | Evaluator: Ken 
      Wilcox Associates |  
    | 
      E-mail:  
      info@franklinfueling.com | 
      Tel: (816) 443-2494 |  
    | URL:  
    www.franklinfueling.com | Date of Evaluation: 
    04/01/08 |    |