Issue Date: April 18, 1997
Revision Date: January 27, 2011
Franklin Fueling Systems
(originally listed as INCON Intelligent Controls, Inc.)
Tank Sentinel TS-1000EFI, TS-1001/TS-2001, and
TS-5xxx Series with TSP-DIS BriteSensor;
Tank Sentinel TS-1000/TS-2000, TS-1001/TS-2001, and TS-5xxx Series with TSP-EIS
Standard Sensor;
Tank Sentinel TS-1000/TS-2000 with TSP-PS Liquid Contact Sensor
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
opto-electric |
Test Results:
|
unleaded
|
synthetic
|
diesel
|
heating
|
|
|
TSP-DIS BriteSensor
|
gasoline
|
gasoline
|
fuel**
|
oil
#2
|
water
|
E85 |
Detection
time (min:sec)
|
03:13
|
03:17
|
3:00
|
3:02
|
03:18
|
-- |
Fall
time (min)
|
<1
|
<1
|
<1
|
<1
|
<1
|
-- |
Product
activation height (cm)
|
1.60
|
N/D*
|
N/D
|
N/D
|
1.92
|
-- |
Lower
Detection Limit (cm)
|
1.60
|
1.60
|
1.50
|
1.50
|
1.62
|
-- |
TSP-EIS Standard Sensor
|
|
|
|
|
|
|
Detection
time (min:sec)
|
03:01
|
03:17
|
3:00
|
3:02
|
03:07
|
<1 |
Fall
time (min)
|
<1
|
<1
|
<1
|
<1
|
<1
|
<1 |
Product
activation height (cm)
|
1.50
|
N/D
|
N/D
|
N/D
|
N/D
|
1.99 |
Lower
Detection Limit (cm)
|
1.50
|
1.60
|
1.50
|
1.50
|
1.50
|
1.99 |
TSP-PS Liquid Contact Sensor
|
|
|
|
|
|
|
Detection
time (min:sec)
|
01:14
|
01:13
|
01:10
|
01:16
|
01:25
|
-- |
Fall
time (min)
|
<1
|
<1
|
<1
|
<1
|
<1
|
-- |
Product
activation height (cm)
|
1.37
|
N/D
|
N/D
|
N/D
|
N/D
|
-- |
Lower
Detection Limit (cm)
|
1.22
|
1.21
|
1.20
|
1.24
|
1.32
|
-- |
*
See glossary.
**This evaluation determined the sensor's responses to the
liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and
biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor
threshold is exceeded. Responses to these fuels were not determined, but
would be expected to be very similar to the diesel responses.
Comments:
Comparison of Tank Sentinel
TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000
(including EFI) / TS-2000 series consoles showed comparable results when
evaluated with representative sensors.
Sensors
are reusable.
Franklin Fueling
Systems
|
Evaluator: Carnegie Mellon Research Institute
|
3760 Marsh Road |
Tel: (412) 268-3495 |
Madison, WI 53718
|
Dates of Evaluations: 12/09/94,
01/30/96, 07/02/93
|
Tel: (800) 225-9787
|
Evaluator: Ken
Wilcox Associates
|
E-mail:
info@franklinfueling.com
|
Tel: (816) 443-2494
|
URL:
www.franklinfueling.com |
Date of Evaluation:
04/01/08, 11/20/10 |
|