Issue Date: April 19, 2001
Revision Date: May 8, 2012
Franklin Fueling Systems
(originally listed as
FE Petro, Inc.)
STP-MLD-HC and STP-MLD-HCD
Pipeline Leak Detectors
(for Rigid, Flexible, or Hybrid Combination of Rigid and Flexible Pipelines)
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel for STP-MLD-HC.
Diesel, Kerosene for STP-MLD-HCD |
Specification |
System tests
pressurized rigid, flexible, and combination of rigid and flexible
pipelines.
Tests are conducted at operating pressure. |
Pipeline
Capacity |
Maximum of 396.6
gallons for rigid pipelines.
Maximum of 95.5 gallons for flexible pipelines.
Maximum combined capacity is 492.1 gallons, not to exceed the above
individual capacity limitations for rigid or flexible pipelines. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing. |
Test
Period |
Response time is
less than 30 seconds. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold. Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Comments |
STP-MLD-HC test
conducted using gasoline in 200 feet of 3.25 inch fiberglass pipe.
STP-MLD-HCD test conducted using diesel in 200 feet of 3.25 inch fiberglass
pipe. |
Franklin Fueling Systems
|
Evaluator:
Ken Wilcox Associates
|
3760 Marsh Road
|
Tel:
(816) 443-2494
|
Madison, WI
53718
|
Dates of Evaluations:
11/07/00, 05/19/06
|
Tel: (800)
225-9787
|
|
E-mail: info@franklinfueling.com |
|
URL: www.franklinfueling.com |
|
|