Issue Date: November 22, 1995
Revision Date: March 24, 2011
Franklin Fueling Systems
(originally listed as
FE Petro, Inc.)
STP-MLD-D
Pipeline Leak Detector
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Diesel |
Specification |
System tests
steel and fiberglass pipelines.
Tests are conducted at operating pressure. |
Pipeline
Capacity |
Maximum for rigid
system is 341 gallons. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing. |
Test
Period |
Average response
time is 1 minute. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline. Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Franklin Fueling Systems
|
Evaluator:
Ken Wilcox Associates
|
3760 Marsh Road
|
Tel:
(816) 443-2494
|
Madison, WI
53718
|
Date of Evaluation:
04/30/94
|
Tel: (800)
225-9787
|
|
E-mail: info@franklinfueling.com |
|
URL: www.franklinfueling.com |
|
|