Estabrook EZY CHEK Systems
(originally
listed as Horner EZY CHEK)
EZY-Chek Manual
Line Leak Detector (for Flexible Pipelines)
LINE TIGHTNESS TEST
METHOD
Certification |
Leak
rate of 0.1 gph with PD = 99.8% and PFA = 0.2%. |
Leak Threshold |
0.05
gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel, aviation fuel, fuel oil #4. |
Specification |
System
tests flexible pipelines.
Tests are conducted at 150% operating pressure.
Mechanical line leak detector must be removed or manually isolated from
pipeline for duration of test, or if testing is to be conducted with
mechanical line leak detector in place, check valve in pump must be manually
closed. |
Pipeline Capacity |
Maximum
of 101 gallons (example: 275 feet of 3 inch line). |
Waiting Time |
None
between delivery and testing. None between dispensing and testing. |
Test Period |
Under
ideal conditions, 30 minutes; actual test time will depend on line size and
temperature conditions at the site.
Data are collected every 15 minutes.
Three consecutive consistent readings are required for a valid test.
Data from the evaluation suggests that the actual minimum test time
for a line this size is 2 hours.
Test data are acquired and recorded manually.
Manual calculations performed by the operator on site. |
Calibration |
No
temperature sensors used.
No calibration required.
System must be checked annually in accordance with manufacturer's
instructions.
Technicians must be certified by the manufacturer prior to using this
equipment, and recertified every two years. |