Issue Date: November 22, 1995
Revision Date: September 10, 2004
Estabrook
EZY CHEK Systems
(originally listed as Horner EZY CHEK)
EZY-Chek I
VOLUMETRIC TANK TIGHTNESS TEST
METHOD (OVERFILL)
Estabrook EZ
Chek Systems no longer manufactures or supports the use of this method.
Certification |
Leak rate of 0.1
gph with PD = 99% and PFA = 1%. |
Leak
Threshold |
0.05 gph.
A tank system should not be declared tight if the test result indicates a
loss or gain that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4. |
Tank
Capacity |
Maximum of 12,000
gallons.
Tank must be minimum 100% full. |
Waiting
Time |
Minimum of 6
hours between delivery and testing. Minimum of 3 hours between
"topping off" and testing.
Total minimum waiting time is 6 hours.
There must be no product dispensing or delivery during waiting time. |
Test
Period |
Minimum of 1
hour, 30 minutes (30 minute monitor period, plus 1 hour test
period).
Testing must continue until data meets manufacturer's stop test
criteria.
Volume data are collected and recorded by a strip chart recorder. Leak
rate is calculated from data of last 1 hour of test period.
There must be no dispensing or delivery during test. |
Temperature |
Average for
product is determined by a resistance temperature detector (RTD) and
displayed on a LCD readout. |
Groundwater |
Depth to
groundwater in tank excavation backfill must be determined.
If groundwater is above bottom of tank, product level must be adjusted to
provide net pressure of 2-4 psi at bottom of tank.
Groundwater level must be stable prior to and during test. |
Calibration |
Level sensors
must be calibrated in accordance with manufacturer's instructions before
each test. |
Comments |
Not evaluated
using manifolded tank systems. |
Estabrook
EZY CHEK Systems
|
Evaluator:
W. A. Kibbe and Associates
|
1505
Woodside Ave.
|
Tel:
(517) 797-2425
|
Essexville,
MI 48732
|
Date of
Evaluation: 10/03/90
|
Tel:
(989) 891-9868
|
|
E-mail: sales@ezychek.com |
|
URL: www.ezychek.com |
|
|