Issue Date: April 18, 1997
Revision Date: March 10, 2000
 

EBW, Inc.

AutoStik Discriminating Sensors
LS-5, LS-10, LS-15, LS-20, LS-35

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

Output type

qualitative

Sampling frequency

continuous

Operating principle

product permeability

 

Test Results:

unleaded gasoline

diesel

water

LS-5, LS-35 (polymer strips)

Detection time (min)

~7

~60

N/A*

Fall time (sec)

N/A

N/A

N/A

Lower detection limit (cm)

<0.014

<0.014

N/A

LS-10, LS-15, LS-20 (polymer strips)

 

 

 

Detection time (min)

~7

~60

N/A*

Fall time (sec)

N/A

N/A

N/A

Lower detection limit (in)

<0.014

<0.014

N/A

*See glossary.

Specificity Results:
Manufacturer and evaluator claim sensors will respond to any liquid, except water.

Manufacturer’s specifications:
Operating temperature: -20 degrees F to 150 degrees F(-28.9 degrees C to 65.5 degrees C).
There is no manufacturer’s recommended maintenance schedule.

Comments:
Sensors can be reset by exposing them to air.
Sensors are reusable.

 

EBW, Inc.

Evaluator:  Ken Wilcox Associates

3760 Marsh Road

Tel:  (816) 443-2494

Madison, WI  53718

Date of Evaluation:  07/05/94

Tel:  (800) 225-9787

 

E-mail:  info@franklinfueling.com  
URL:  www.ebw.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.