Issue
Date: January 11,
2001
Revision Date: December 21, 2010
Containment
Solutions, Inc.
(originally listed as Fluid Containment and O/C Tanks)
FOVF 600B, FOVF
600S Non-Discriminating Sensors for High Level Overfill (Brass, Steel); FCBS 700
Non-Discriminating Sensor for Collars, Bulkheads, Sumps; FDAS 710
Non-Discriminating Sensor for Dry Annular Spaces; FHRB 810 Non-Discriminating
Sensor for Reservoirs
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
Output type: |
qualitative
|
Sampling frequency: |
continuous
|
Operating
principle: |
float
switch |
Test
Results:
Non-Discriminating Sensors
|
unleaded
gasoline
|
diesel*
|
water
|
FOVF
600B, FOVF 600S (Overfill)
|
|
|
|
Lower Detection Limit (in)
|
3.32
|
3.26
|
3.18
|
Precision-Standard Deviation
(in)
|
0.0051
|
0.0025
|
0.0037
|
Detection time (sec)
|
<1
|
<1
|
<1
|
Fall time (sec)
|
<1
|
<1
|
<1
|
FCBS
700 (Collars, Bulkheads,Sumps)
|
|
|
|
Lower Detection Limit (in)
|
0.99
|
0.97
|
0.87
|
Precision-Standard Deviation
(in)
|
0.0040
|
0.0027
|
0.0043
|
Detection time (sec)
|
<1
|
<1
|
<1
|
Fall time (sec)
|
<1
|
<1
|
<1
|
FDAS
710 (Dry Annular Spaces)
|
|
|
|
Lower Detection Limit (in)
|
0.44
|
0.43
|
0.42
|
Precision-Standard Deviation
(in)
|
0.0025
|
0.0041
|
0.0031
|
Detection time (sec)
|
<1
|
<1
|
<1
|
Fall time (sec)
|
<1
|
<1
|
<1
|
FHRB 810
(Reservoirs - Low level float)
|
|
|
|
Lower Detection Limit (in)
|
2.57
|
2.53
|
2.31
|
Precision-Standard Deviation
(in)
|
0.0042
|
0.111
|
0.0042
|
Detection time (sec)
|
<1
|
<1
|
<1
|
Fall time (sec)
|
<1
|
<1
|
<1
|
FHRB
810 (Reservoirs - High level float)
|
|
|
|
Lower Detection Limit (in)
|
13.31
|
13.24
|
13.01
|
Precision-Standard Deviation
(in)
|
0.0080
|
0.0061
|
0.0042
|
Detection time (sec)
|
<1
|
<1
|
<1
|
Fall time (sec)
|
<1
|
<1
|
<1
|
*This evaluation determined the sensors’ responses to the liquids
shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100
meeting ASTM D6751 would also produce an alarm if the sensor threshold is
exceeded. Responses to these fuels were not determined, but would be expected
to be very similar to the diesel responses.
Comments:
Control panel
models:
CPF 1, CPF 2, CPF 3, CPF 4 for liquid level sensors;
CPI 1D, CPI 1H, CPI 1N inventory
control for liquid level sensors and 1 tank;
CPD 1, CPD 2, CPD 4 for discriminating liquid level sensors;
CPI 4 inventory control for liquid level sensors and up to 4 tanks;
BOMC battery operated control cap for liquid level sensors;
CCF 1DA battery operated control cap for dry annulus monitoring;
CCF
2 battery operated control cap for hydrostatic reservoir monitoring.
Containment Solutions, Inc.
|
Evaluator:
Ken Wilcox Associates
|
5150 Jefferson Chemical
|
Tel: (816) 443-2494
|
Conroe, TX 77301-6834
|
Date of Evaluation:
06/11/99
|
Tel: (800) 628-2657
|
|
E-Mail: dheiman@csiproducts.com |
|
URL: www.containmentsolutions.com |
|
|