| Issue Date: November 22, 1995Revision Date: 
April 28, 2005
 Campo/Miller,
Inc. LS300, LS300 N/C, LS300-120,
LS300-120 XLC, LS300-120 PLUS, LS300-120 PLUS A/S AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR 
  
    | Certification | 
    Leak rate of 3.0 gph at 10 psi* with PD = 96.2% and PFA = 0%.*Since 
    leak rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak
      Threshold | 2.36 gph. A pipeline system should not be declared tight if the test result
      indicates a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuels, fuel oil #4, waste oil, kerosene. |  
    | Specification | System tests
      pressurized fiberglass and steel pipelines. Tests are conducted at operating pressure.
 |  
    | Pipeline
      Capacity | Maximum of 35.36
      gallons. |  
    | Waiting
      Time | None between
      delivery and testing. None between dispensing and testing.
 |  
    | Test
      Period | Response time is
      10 seconds for LS300, LS300 N/C. Response time is 10 seconds, but can be adjusted between 10 seconds and 2
      minutes, 30 seconds depending on the bulk modulus* of the piping system
      for LS300-120, LS300-120 XLC, LS300-120 PLUS, LS300-120 PLUS A/S.
 Test data are acquired and recorded by a microprocessor.
 *See glossary.
 |  
    | System
      Features | Permanent
      installation on pipeline. Automatic testing of pipeline.
 Preset leak threshold.
 Single leak test to determine if pipeline is leaking.
 Pump shutdown, indicator light and alarm activation if leak is declared.
 Pump control, line 
    pressure display, alarm and test logs. |  
    | Calibration | Manufacturer
      recommends a weekly self check, activated by the operator, and a full
      functional test every 30 days, estimated to take 5 minutes to perform for
      LS300, LS300 N/C, LS300-120, LS300-120 XLC. System must be checked annually and, if necessary, calibrated in
      accordance with manufacturer's instructions for LS300-120 PLUS, LS300-120
      PLUS A/S .
 |    
  
    | Campo/Miller,
      Inc.
      
      
       | Evaluator: 
      Jetronix Engineering Laboratories
      
      
       |  
    | P. O.
      Box 1809
      
      
       | Tel: 
      (213) 377-4668
      
      
       |  
    | Porterville,
      CA 93258
      
      
       | Date of
      Evaluation:  06/01/91
      
      
       |  
    | Tel: 
      (209) 781-6862
      
      
       | Evaluator: 
      Ken Wilcox Associates
      
      
       |  
    |  
      
      
       | Tel: 
      (816) 443-2494
      
      
       |  
    |  
      
      
       | Date of
      Evaluation:  09/09/94 
      
      
       |  |