Issue Date: April 18, 1997
Revision Date: December 26, 2007

AT Monitors 
(originally listed as Armstrong Monitoring, Corp. and then Sequence Controls, Inc.)

AMC 5100 or ATI-5100 Monitor with
Vapor Sensors AMC F4000 or ATI-F4000

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

 

Detector:           

 Output type:

qualitative

 Sampling frequency:

continuous

 Operating principle:

metal oxide semiconductor

Test Results:

AMC F4000

benzene

Detection time (sec):

10

Fall time (min:sec):

04:02

Lower detection limit (ppm):

300

Comments:
Sensors are reusable.

 

Armstrong Technologies Inc.

Evaluator:  Environment Canada

14 Birch Drive

Tel:  (613) 991-4568

Kemptville, Ontario K0G 1J0 Canada

Date of Evaluation:  12/03/92

Tel:  (613) 258-5225

 

E-mail:  info@atmonitors.com  
URL www.atmonitors.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.