Issue Date: May 16, 2019
ASIS Automation and Fueling Systems, Inc.
FOX SIR V1 and V2
STATISTICAL INVENTORY
RECONCILIATION TEST METHOD (QUANTITATIVE)
Certification |
Leak rate of 0.2 gph with PD > 99.9 % and PFA < 0.1% (Version 2).
Leak rate of 0.1 gph with PD = 96.5% and PFA = 3.5% (Version 1). |
Leak
Threshold |
0.1 gph for leak rate of 0.2 gph (Version 2).
0.05 gph for leak rate of 0.1 gph (Version 1).
A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the threshold level of the version selected. |
Applicability |
Gasoline, diesel. |
Tank
Capacity |
Maximum of 20,000 gallons for single tank.
Maximum of 60,000 gallons cumulative capacity for manifolded tank systems with no more than 4 tanks in system. |
Throughput |
Maximum monthly throughput of 115,000 gallons. |
Data
Requirement |
Minimum of 30 days of product level and flow through data.
This method allows for closure of the station up to 2 days per week.
This method does not require meter calibration. |
Comments |
63% of data sets evaluated were from manifolded tank systems.
Of 41 data sets submitted for evaluation, 5 had inconclusive results with 2 coming from single tank systems and 3 coming from 2-tank manifold systems.
Median monthly throughput of tanks evaluated was 20,086 gallons.
Leak rates of 0.1, 0.2, and 0.3 gph were used in the evaluation.
Data sets evaluated were randomly selected from a database of inventory records maintained by evaluator. |
ASIS Automation and Fueling Systems, Inc.
|
Evaluator: Ken Wilcox Associates
|
Tatlisu Mahallesi Akif Inan Sokak No: 14 |
Tel: (816) 443-2494
|
Istanbul, Turkey 34775 |
Dates of
Evaluation: April 3, 2019
|
Phone: +90 216 540 6464 |
|
E-mail: info@asis.com.tr |
|
|