Issue Date: January 31, 2019 Revision Date:
April 13, 2022
AC’CENT Environmental
Dri-Sump Containment Tightness Test Method
SECONDARY AND SPILL CONTAINMENT TEST METHOD
Certification |
Leak rate of 0.1 gph with PD = 100%, and PFA = 0%
Please be aware that the authority having jurisdiction in your particular state, territory, tribe or municipality may have set a minimum detectable leak rate for secondary and spill containment testing.
|
Applicability |
For testing spill and sump containments that are free of debris or measurable liquid, located in non-saturated backfill consisting of sand, pea gravel, or clay/silt.
|
Specification |
Containment must be free of
debris and measurable liquid. Containment backfill can be moist but not
saturated with measurable liquid as verified by visual observation of liquid
level in Vapor Stimulator Tubes (VST) or if the sump bottoms are deeper than
the VST through observation wells located in the containment backfill.
VSTs shall be installed per manufacturer’s installation training and
certification procedures and instructions which include the minimum number
of VSTs, placement and depth for each type of containment. Dri-sump test
equipment and technicians must be current in certifications through ACCENT
or its authorized representative.
Vapor Stimulator Tubes (VST) Placement Chart
Containment Sump Type |
Minimum Number of VSTs per Containment Sump |
Maximum Horizontal Distance from Sump Wall |
Minimum Length of VST |
Backfill Soil Type Acceptance |
Minimum Test Time for pass or fail results |
Spill Bucket |
1 |
8 inches
(±1”) |
18 inches |
All |
1 minute |
Under Dispenser Containment Sump (UDC) |
1 |
8 inches
(±1”) |
18 inches |
All |
1 minute |
Transition Sump (UDC depth) |
1 |
8 inches
(±1”) |
18 inches |
All |
1 minute |
Transition Sump (STP depth) |
2 |
8 inches
(±1”) |
36 inches |
All |
1 minute |
Submersible Turbine Sump (STP) |
2 |
8 inches
(±1”) |
36 inches |
All |
1 minute |
|
Pre-test Verification |
A manometer is used to indicate
adequate air flow and communication between VSTs in a 5-10 second pre-test
procedure. Communication will be verified between two VSTs within the tank,
piping, and dispenser in the same type backfill. |
Waiting
Time |
No waiting time before test begins. |
Test
Period |
Minimum of one minute once the
test begins. Test data and any associated telemetry are required to be in
the current report format (e.g. written, online, cloud-based, etc.) designed
by ACCENT or its authorized representative. |
System
Features |
A leak is determined by
observation through one of two view ports for a change in the specialized
digital laser light beam from a “dot” to a “ line”, which is indicative of
the presence of the proprietary heavy vapor. Either view port can be used to
see the laser, or a smart phone or other visual aid can be used from outside
the view chamber. |
Comments |
All consumables (e.g., VSTs
and Aerosol) are manufactured exclusively by AC’CENT or its authorized
representative. Dri-sump Containment Tightness Test method uses the
proprietary heavy vapor aerosol instead of water to completely fill the
sump, interstice or vessel. AC’CENT states this proprietary vapor
aerosol is made from a formula of chemicals which are all food grade, pH
neutral, non-petroleum based, non-toxic, non-flammable, and pose no
environmental impact. The dissipation of the aerosol reverts back to normal
organic elements in ambient air. When installed per the manufacturer’s
placement requirements this method allows for detecting heavy vapor egress
from the containment at any point. The method automatically tests for
adequate flow of air and vapor through the backfill each time the system is
activated. Any stoppage of flow through the VST or backfill will cause
increased vacuum on the View Chamber that is quickly identified by a
significant collapse of the View Chamber side walls. Temperature is not a
factor.
The evaluation testing was conducted with three different
non-metallic commercially manufactured deep containment sumps, 300 gallon
capacity, 47 inches diameter and 60 inches long. These were installed as
would typically be found at a fuel service station. They were tested in
different backfill types, including: sand; pea gravel, and clay/silt mix.
The presence of water above the bottom of the sumps was not evaluated.
|
Danny Brevard, PG
|
Evaluator:
Ken Wilcox Associates
|
AC'CENT Corporate Offices
|
1125 Valley Ridge Dr
|
P. O. Box 3289
|
Grain Valley, MO 64029
|
Lufkin, TX 75903-3289
|
Tel: (816) 443-2494
|
E-mail: info@info@accent-us.com |
Dates of Evaluations: 10/04/18 |
URL:
www.accent-us.com |
|
|
Home |
Vendors: A - F |
Vendors: G - M |
Vendors: N - S |
Vendors: T - Z |
Method Index |
Glossary |
Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations. For full details, please refer to our expanded "DISCLAIMER"
page.
| |