| Issue Date: November 10, 2021
 
 Pneumercator
Company, Inc. LLP-203 Series 
Pipeline Line Leak Detector with the TMS2000, TMS3000 and TMS4000 Series Consoles for Hourly Testing on Rigid, Flexible and Hybrid Pipelines
 AUTOMATIC ELECTRONIC LINE LEAK 
DETECTOR  
  
    | Certification | Leak rate of 3.0 
	gph @ 10 psi equivalent with PD = 100% and PFA = 0% |  
    | Leak
      Threshold | 1.8 gph at 10 psi 
	equivalent. A pipeline system should not be declared tight if the test 
	result indicates a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel, 
	aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 
	meeting ASTM D7467, biodiesel B100 meeting ASTM D6751, #4 and #6 fuel oil, 
	used oil. |  
    | Specification | Mystem tests 
	pressurized Fiberglass, flexible, semi-rigid and rigid pipelines. Tests 
	are conducted at system operating pressure.
 |  
    | Pipeline Capacity | If the desired 
	Bulk Modulus value does not appear in the table, select the next LOWER 
	value. If the desired Charge (system operating) Pressure value does not 
	appear in the table, select the next HIGHER value. |  
    |  |  |  
    | Waiting Time | Waiting times 
	after the delivery of product, after product is circulated through the line 
	or after pumping has stopped are not necessary before valid tests can be 
	conducted. |  
    | Test 
	Period | Response time is 
	dependent on line volume, service pressure, and bulk modulus, and can range 
	from 30 seconds to 13 minutes. |  
    | System Features | Permanent 
	installation on pipeline. Automatic testing of pipeline.
 Preset 
	threshold.
 Single test to determine if pipeline is leaking.
 If 
	leak is declared: Programmable for alarm only, or alarm with system 
	shutdown. Programmable for test following pump shutdown only, or hourly.
 |  
    | Calibration | Leak Detection 
	system operation must be verified annually in accordance with manufacturer's 
	instructions. |  
    | Comments |  |    
  
    | Pneumercator Company, Inc.
      
             | Evaluator: 
      Ken Wilcox Associates
      
             |  
    | 1785 Expressway Drive North
                
             | Tel:  (816) 443-2494
      
             |  
    | Hauppauge, NY 11788
                
       | Date of Evaluation: 
      04/29/2021, 10/28/2021 |  
    | Tel:  (800) 209-7858, (631) 293-8450 x112 |  |  
    | E-mail:   jlevy@pneumercator.com
                
       |        |  