Issue Date: November 10, 2021
Pneumercator
Company, Inc.
LLP-203 Series
Pipeline Line Leak Detector with the TMS2000, TMS3000 and TMS4000 Series
Consoles for Hourly Testing on Rigid, Flexible and Hybrid Pipelines
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph @ 10 psi equivalent with PD = 100% and PFA = 0% |
Leak
Threshold |
1.8 gph at 10 psi
equivalent. A pipeline system should not be declared tight if the test
result indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20
meeting ASTM D7467, biodiesel B100 meeting ASTM D6751, #4 and #6 fuel oil,
used oil. |
Specification |
Mystem tests
pressurized Fiberglass, flexible, semi-rigid and rigid pipelines. Tests
are conducted at system operating pressure. |
Pipeline Capacity |
If the desired
Bulk Modulus value does not appear in the table, select the next LOWER
value. If the desired Charge (system operating) Pressure value does not
appear in the table, select the next HIGHER value. |
|
|
Waiting Time |
Waiting times
after the delivery of product, after product is circulated through the line
or after pumping has stopped are not necessary before valid tests can be
conducted. |
Test
Period |
Response time is
dependent on line volume, service pressure, and bulk modulus, and can range
from 30 seconds to 13 minutes. |
System Features |
Permanent
installation on pipeline. Automatic testing of pipeline. Preset
threshold. Single test to determine if pipeline is leaking. If
leak is declared: Programmable for alarm only, or alarm with system
shutdown. Programmable for test following pump shutdown only, or hourly. |
Calibration |
Leak Detection
system operation must be verified annually in accordance with manufacturer's
instructions. |
Comments |
|
Pneumercator Company, Inc.
|
Evaluator:
Ken Wilcox Associates
|
1785 Expressway Drive North
|
Tel: (816) 443-2494
|
Hauppauge, NY 11788
|
Date of Evaluation:
04/29/2021, 10/28/2021 |
Tel: (800) 209-7858, (631) 293-8450 x112 |
|
E-mail: jlevy@pneumercator.com
|
|
URL: www.pneumercator.com |
|