Issue Date: February 8, 2010
Cambria Corporation
Models EOS80, EOS100, and EOS120 Discriminating Sensors with Beaudreau Electric, Inc.'s Models 522 Remote Monitoring System
and Model 522T Monitoring System, and Cambria Mark I Monitoring System
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output type |
qualitative, discriminating |
Sampling frequency |
continuous |
Operating principle |
Evanescent wave absorption / refractive index of liquids |
Test Results:
Model EOS80
(single sensing level) |
0.05 inch of unleaded
gasoline |
water |
Minimum alarm level (inch) |
<0.01 |
<0.01 |
Maximum level (feet) |
<90 |
<90 |
Model
(5 sensing levels) |
|
|
Detection time (sec) |
<1 |
<1 |
Fall time |
<1 |
<1 |
Lower detection limit (in) |
||
Level 1 (low level switch) |
0.562 |
0.561 |
Level 2 |
1.235 |
no data |
Level 3 |
2.081 |
no data |
Level 4 |
2.903 |
no data |
Level 5 (high level switch) |
3.580 |
3.614 |
Specificity
Results:
Manufacturer and evaluator claim
sensors will respond to any liquid after its threshold is exceeded.
Testing was specifically conducted for performance in water and water with a thin layer of fuel.
Manufacturer’s
Specifications:
Can be installed on any control device that accepts TS232 communication
from the sensor.
Models EOS100 and EOS120 sensors identify liquid in a range from nominal depth of 0.5 inch to 3.5 inches at 0.75 inch increments.
The Model EOS120 sensor is designed to be a drop-in replacement for the Model EOS100 sensor.
Comments:
*The position of the Model EOS80 sensor can be adjusted for any depth of
liquid required.
Cambria Corporation |
Evaluator:
Ken Wilcox Associates |
1328 North 128th Street |
Tel: (816) 443-2494 |
Seattle, WA 98133 |
Date of Evaluation: 09/08/09 |
Tel: (206) 782-8330 |
|
E-mail: sales@cambriasensors | |
URL: www.cambriasensors.com |